AQUAFORCE® 30XA
150Pages

{{requestButtons}}

Catalog excerpts

AQUAFORCE® 30XA - 1

Product Data AQUAFORCE® 30XA080-500 Air-Cooled Liquid Chillers 80 to 500 Nominal Tons (265 to 1615 Nominal kW) ® AquaForce chillers were designed from the ground up to meet the efficiency demands of today and the future by providing premium aircooled chiller packages for contractors, consulting engineers and building owners. • Rotary screw compression • R-134a HFC refrigerant • Quiet AeroAcoustic™ fan system • Novation® heat exchanger technology with microchannel coil • Easy to use ComfortLink controls • Optional integrated hydronic pump package, available with variable frequency drive (VFD) Features/Benefits AquaForce 30XA chillers provide best full load and part load performance in a single chassis from 80 to 500 tons Premium performance a30-4024 Well exceeds ASHRAE 90.1 Standards. Aqua series chillers are Carrier’s most efficient air-cooled models. The AquaForce chiller is one of the most affordable air-cooled chillers to operate and maintain. The AquaForce chiller offers full load EER (Energy Efficiency Ratio) up to 10.9 and IPLV (Integrated Part Load Value) up to 15.5 with Novation heat exchanger technology. Highefficiency rotary screw compressors with infinitely variable slide valves allow the chillers to exactly match actual load conditions, delivering exceptional part load performance. The AquaForce chillers deliver superior efficiency through the entire operating range to keep costs and demand charges down. This exceptional performance has a significant impact on energy savings and cost of ownership. Form 30XA-12PD

Open the catalog to page 1
AQUAFORCE® 30XA - 2

Features/Benefits (cont) AquaForce® chillers’ quiet operation make them ideal for sound sensitive applications Great performance is delivered in a low sound unit that will be quiet enough for any application including hospitals, schools and other sites located in residential neighborhoods. The AquaForce chiller’s AeroAcoustic™ fan is almost twice as quiet per cfm as the competition. In part load operation, such as cooler weather or night time duty, fewer fans operate. This results in even quieter operation. Built in reliability AquaForce chillers were developed under one of the most...

Open the catalog to page 2
AQUAFORCE® 30XA - 3

Novation® heat exchanger technology The Novation heat exchanger design with microchannel (MCHX) condenser coil is a robust, cost effective alternative to traditional coil design. These coils are offered coated or uncoated to match coil protection to site conditions. The Carrier Electronic Catalog (E-Cat) can be used to determine whether or not corrosion protection is recommended for particular applications in coastal/marine environments. Following the input of the requested data, the E-Cat program output will advise the appropriate coil to be used. Other factors described in "Selection...

Open the catalog to page 3
AQUAFORCE® 30XA - 4

Model number nomenclature A 30XA – AquaForce® Air-Cooled Chiller 30XA –Design Series Air-Cooled Chiller AquaForce® Unit Sizes* Condenser Coil/Ambient/Low Sound Options Voltage – Aluminum Fin/Copper Tube, High Ambient Temperature 0 – Copper Fin/Copper Tube, High Ambient Temperature 6 – 460-3-60 1 – 575-3-60 1 – Aluminum Pre-Coat Fin/Copper Tube, High Ambient Temperature 7 – 200-3-60 2 – 380-3-60 2 – Aluminum E-Coat Fin/Copper Tube, High Ambient Temperature 4 – 230-3-60 3 – Copper E-Coat Fin/Copper Tube, High Ambient Temperature 4 – Novation® Heat Exchanger (MCHX), High Ambient Temperature...

Open the catalog to page 4
AQUAFORCE® 30XA - 5

SEE PREVIOUS PAGE FOR REMAINDER OF MODEL NUMBER NOMENCLATURE Refrigeration Circuit Options - – None 0 – Suction Line Insulation 1 – Isolation Valves 2 – Low Ambient Head Pressure Control 3 – Suction Line Insulation, Isolation Valves 4 – Suction Line Insulation, Low Ambient Head Pressure Control 5 – Isolation Valves, Low Ambient Head Pressure Control 6 – Suction Line Insulation, Isolation Valves, Head Pressure Control 7 – Minimum Load Control 8 – Suction Line Insulation, Minimum Load Control 9 – Isolation Valves, Minimum Load Control B – Low Ambient Head Pressure Control Operation, Minimum...

Open the catalog to page 5
AQUAFORCE® 30XA - 6

CAPACITY Tons FULL LOAD COOLER FLOW RATE COOLER PRESSURE DROP FULL LOAD COOLER PRESSURE DROP LEGEND Aluminum Coefficient of Performance Copper Energy Efficiency Ratio Integrated Part Load Value Microchannel Heat Exchanger *Air Conditioning, Heating, and Refrigeration Institute (U.S.A.). NOTES: 1. Rated in accordance with AHRI Standard 550/590 at standard rating conditions. 2. Standard rating conditions are as follows: Cooler Conditions: Leaving water temperature: 44 F (6.7 C) Flow rate: 2.4 gpm/ton (0.043 l/s per kW) Fouling Factor: 0.00010 hr x sq ft °F/Btu (0.000018 m2 x °C/W) Condenser...

Open the catalog to page 6
AQUAFORCE® 30XA - 7

Physical data 30XA080-122 — ENGLISH UNIT 30XA OPERATING WEIGHT (lb)* Al-Cu Condenser Coils Cu-Cu Condenser Coils MCHX Condenser Coils REFRIGERANT TYPE Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C (MCHX) COMPRESSORS Quantity Speed (rpm) (Qty) Compressor Model Number Ckt A (Qty) Compressor Model Number Ckt B (Qty) Compressor Model Number Ckt C Oil Charge (gal), Ckt A/Ckt B/Ckt C Minimum Capacity Step (%) Standard Optional COOLER Net Fluid Volume (gal.) Maximum Refrigerant Pressure (psig) Maximum Water-Side Pressure without Pumps (psig) Maximum Water-Side...

Open the catalog to page 7
AQUAFORCE® 30XA - 8

Physical data (cont) 30XA222-302 — ENGLISH UNIT 30XA OPERATING WEIGHT (lb)* Al-Cu Condenser Coils Cu-Cu Condenser Coils MCHX Condenser Coils REFRIGERANT TYPE Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C (MCHX) COMPRESSORS Quantity Speed (rpm) (Qty) Compressor Model Number Ckt A (Qty) Compressor Model Number Ckt B (Qty) Compressor Model Number Ckt C Oil Charge (gal), Ckt A/Ckt B/Ckt C Minimum Capacity Step (%) Standard Optional COOLER Net Fluid Volume (gal.) Maximum Refrigerant Pressure (psig) Maximum Water-Side Pressure without Pumps (psig) Maximum...

Open the catalog to page 8
AQUAFORCE® 30XA - 9

OPERATING WEIGHT (kg)* Al-Cu Condenser Coils Cu-Cu Condenser Coils MCHX Condenser Coils REFRIGERANT TYPE Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C (MCHX) COMPRESSORS Quantity Speed (r/s) (Qty) Compressor Model Number Ckt A (Qty) Compressor Model Number Ckt B (Qty) Compressor Model Number Ckt C Oil Charge (liters), Ckt A/Ckt B/Ckt C Minimum Capacity Step (%) Standard Optional Net Fluid Volume (liters) Maximum Refrigerant Pressure (kPa) Maximum Water-Side Pressure without Pumps (kPa) Maximum Water-Side Pressure with Pumps (kPa) WATER CONNECTIONS Drain...

Open the catalog to page 9

All Carrier| Commercial Systems North America catalogs and technical brochures

  1. Axis™

    2 Pages

  2. AHUBuilder

    2 Pages

  3. 50ZPB

    4 Pages

  4. 39CC

    2 Pages

  5. 48PG CENTURION?

    107 Pages

  6. 48XL-A

    30 Pages

  7. OMNIZONE?

    80 Pages

  8. 16TJ

    32 Pages

  9. 39S

    36 Pages

  10. 39L AERO®

    52 Pages

  11. 39M AERO®

    110 Pages

Archived catalogs