Product Data 36CBAL,CBAJ Series Active Chilled Beams 8 to 180 cfm
カタログの1ページ目を開く
Features/Benefits Chilled beam systems are suitable for use in sensible cooling load applications where individual temperature control is required. Active chilled beam units offer: • Precise control of ventilation airflow • Sensible cooling and heating options Active chilled beam systems An active chilled beam takes a source of primary air at an inlet static pressure ranging from 0.2 to 0.8 in. wg. It distributes this air through a bank of specially designed aerodynamic nozzles and discharges the air at a high velocity into a mixing chamber. This creates a differential pressure which...
カタログの2ページ目を開く
36CB A L C B 2 EGOY GAYYY 36CB - Chilled Beam Design Revision A - Current Design Product Style J - 1-Way Linear Slot L - 2-Way Linear Slot Unit Size - Footprint (in.) B - 48 X 24 C - 24 X 24 E - 72x24 F - 96 x 24 (36CBAL) (ETO) Nozzle Type A - 1-Row, 24-Size B - 2-Row, 24-Size C - 1-Row, 31-Size D - 2-Row, 31-Size E - 1-Row, 38-Size F - 2-Row, 38-Size G - 1-Row, 18-Size H - 2-Row, 18-Size System Type 2 - 2-Pipe, 2-Row Coil 5 - 4-Pipe, 2-Row Coil with Split Circuiting Primary Air Configuration E - End C - Center Piping Configurations B - Right Hand (2-Pipe) C - Left Hand (2-Pipe) G - Same...
カタログの3ページ目を開く
Factory-installed options Factory-installed options Induction nozzles are available in various sizes to match capacity requirements. Coils are available in 2-pipe or 4-pipe configurations. Grilles are available in various colors with perforated return and slot supply. The grille is hinged with easy access latches. Face and trim of the grille are painted standard white color. Optional insulation on the unit exterior (inlcuding the primary air tube) is recommended when the primary air temperature supplied to the unit is below 55°F. The optional insulation used is Armacell Model AP sheet...
カタログの4ページ目を開く
36CBAL, 2-PIPE, SIZE 02 UNIT DIMENSIONS - 0 PRIMARY AIR END CONNECTION HANGER BRACKET - LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.
カタログの5ページ目を開く
Dimensions (cont) 36CBAL, 2-PIPE, SIZE 04 UNIT DIMENSIONS Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicate
カタログの6ページ目を開く
36CBAL, 2-PIPE, SIZE 06 UNIT DIMENSIONS HANGER BRACKET- LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.
カタログの7ページ目を開く
Dimensions (cont) 36CBAL, 4-PIPE, SIZE 02 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicate
カタログの8ページ目を開く
36CBAL, 4-PIPE, SIZE 04 UNIT DIMENSIONS -6"0 PRIMARY AIR CONNECTION 1/2" COPPER CWS HANGER BRACKET LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.
カタログの9ページ目を開く
1/2" COPPER CWS-HANGER BRACKET- LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.
カタログの10ページ目を開く
36CBAJ, 2-PIPE, SIZE 02 UNIT DIMENSIONS 6"0 PRIMARY AIR END CONNECTION PRESSURE TAP — Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.
カタログの11ページ目を開く
Dimensions (cont) 36CBAJ, 2-PIPE, SIZE 04 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated
カタログの12ページ目を開く
36CBAJ, 2-PIPE, SIZE 06 UNIT DIMENSIONS PRESSURE TAP-1 6"0 PRIMARY AIR END CONNECTION 1/2 71.75 " COPPER CWS HANGER BRACKET 1/2" COPPER HWR 6"0 PRIMARY AIR CONNECTION 1/2" COPPER CWR Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.
カタログの13ページ目を開く
Dimensions (cont) 36CBAJ, 4-PIPE, SIZE 02 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated
カタログの14ページ目を開く
36CBAJ, 4-PIPE, SIZE 04 UNIT DIMENSIONS Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.
カタログの15ページ目を開く
Dimensions (cont) 36CBAJ, 4-PIPE, SIZE 06 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated
カタログの16ページ目を開く
Selection procedure Refer to Carrier Electronic Selection Program or contact your Carrier representative to determine unit size for your application. Application data Systems with chilled beams are suitable for use in sensible cooling load applications and/or where there is a requirement for individual temperature control. In offices with normal room heights, the maximum cooling capacity is 25 to 30 Btuh per sq ft of floor area. The limit is set by the maximum permissible velocity in the occupied zone, therefore high room heights can provide the opportunity for supplying a greater cooling...
カタログの17ページ目を開く
Application data (cont) DOUBLE USE OF THE WATER COOLING TOWER MIXING VALVE 58 F WATER 57 F WATER CHILLED BEAMS WATER COOLED CHILLERS SECONDARY WATER LOOP Dehumidifier Heat Pipe 95 F Air 45 F Water T Stat 45 F Water Heat Exchanger
カタログの18ページ目を開く
SEPARATE SYSTEMS ALTOGETHER Individual Zone Control 55 F Air T Stat Improved COP with warmer water
カタログの19ページ目を開く
Guide specifications Active Chilled Beams HVAC Guide Specifications Size Range: 2, 4, and 6 ft Carrier Model Number: 36CBAL,J Part 1 — General 1.01 SYSTEM DESCRIPTION A. Integrated chilled beam system for ventilation, cooling, and heating. B. Chilled beam unit shall be constant volume primary airflow unit designed to induce a secondary airflow within the conditioned space using the primary conditioned air supply. Capacities and characteristics as listed in the schedule and the guide specifications that follow. 1.02 QUALITY ASSURANCE A. Unit coils shall be tested in general accordance with...
カタログの20ページ目を開くCarrier| Commercial Systems North Americaのすべてのカタログと技術パンフレット
-
WeatherMaker® 50TCQ
116 ページ
-
INFINITY™ 38MPRA
2 ページ
-
ACTIVAIR™ 36IB
44 ページ
-
Axis™
2 ページ
-
AHUBuilder
2 ページ
-
PERFORMANCE™ 50VL-A
6 ページ
-
50ZPB
4 ページ
-
PERFORMANCE™ 50VT-A
6 ページ
-
39CC
2 ページ
-
A World of Comfort
2 ページ
-
48P WEATHERMASTER®
168 ページ
-
48A WEATHERMAKER®
116 ページ
-
48PG CENTURION?
107 ページ
-
48PM CENTURION?
64 ページ
-
48TC WEATHERMAKER®
116 ページ
-
48HC WEATHERMASTER®
124 ページ
-
48LC WEATHEREXPERT®
52 ページ
-
48VL Performance? 14
32 ページ
-
48XL-A
30 ページ
-
48XL Infinity? 15
26 ページ
-
OMNIZONE?
80 ページ
-
16TJ
32 ページ
-
AQUAFORCE® 30XW150-400
60 ページ
-
EVERGREEN® 23XRV
32 ページ
-
AQUAFORCE® 30XA
150 ページ
-
30RB AQUASNAP®
92 ページ
-
30RAP AQUASNAP®
88 ページ
-
39S
36 ページ
-
39L AERO®
52 ページ
-
39M AERO®
110 ページ
-
19XR EVERGREEN®
56 ページ