BMK6000

BMK6000

BMK6000

Product catalog summary
Overview: The AERCO Benchmark 6000 is a condensing hydronic boiler designed for closed-loop systems. It offers a 15:1 burner turndown ratio, allowing it to efficiently match energy input to system demands, optimizing seasonal efficiency. The compact design (79”H x 34”W x 108”D) allows for high capacity in a small footprint.
Features: The boiler supports natural gas or dual fuel (propane) and includes standard oxygen level (O2) monitoring. It maintains NOx emissions at 20 ppm or less across all firing rates. The stainless steel fire tube heat exchanger and variable primary flow capability enhance its performance. It also supports ducted combustion air and offers easy access for maintenance.
Control and Monitoring: The BMK6000 can be controlled via constant setpoint, indoor/outdoor reset, or a 4-20mA signal. It supports Modbus communication for integration with AERCO’s boiler management system or other building automation systems. The real-time O2 monitoring can be remotely accessed, providing insights into emissions and fuel economy.
Specifications: The boiler operates at ASME working pressures of 80 or 150 PSIG and offers electrical options of 208/3/60 30 AMP or 460/3/60 15 AMP. Gas requirements include a minimum of 14” W.C. at full load for both natural gas and propane. Water connections are 6” flanged 150lb ANSI, with a minimum/maximum water flow of 75gpm/600gpm and a water pressure drop of 4.0psig at 570GPM. The control range is 50°F to 190°F, and it operates in ambient temperatures from 0°F to 130°F.
Ratings and Dimensions: The BMK6000 has an input of 6000 MBH and an output of 5670 MBH with an AHRI certified efficiency of 94.5%. It has a water volume of 110 gallons and weighs 3,000 lbs dry and 3,920 lbs wet, with a shipping weight of 3,800 lbs.
Compliance and Approvals: The boiler is compliant with UL, CUL, CSD-1, and ASME standards and offers FM compliant gas train options.
See more

Catalog excerpts

BMK6000-1

BMK SERIES TECHNICAL DATA SHEET Benchmark 6000 Condensing Hydronic Boilers The AERCO Benchmark 6000 Water Boiler is designed for condensing application in any closed loop hydronic system. It delivers 15:1 burner turndown to match energy input directly to fluctuating system loads to yield the highest possible seasonal efficiencies. And no other product packs as much capacity into such a small footprint. To minimize emissions, the BMK6000 is fitted with a low NOx burner whose emissions will consistently measure <20 ppm of NOx corrected to 3% excess oxygen at all firing rates. The fully modulating burner also maintains AERCO standards for energy efficiency, longevity, reliability and construction quality. The BMK6000 comes standard with AERCO’s Patent Pending, Oxygen Level (O2) monitoring system. This monitoring system, designed to display the O2 level directly on the unit in real time, can also be remotely monitored via Modbus giving the customer the ability to measure the emissions level and fuel economy of the boiler without traditional combustion calibration devices. The BMK6000 can be used as an individual unit or in modular arrangements and offers selectable modes of operation. In addition to controlling the boiler according to a constant set point, indoor/outdoor reset schedule or 4-20mA signal, one or more units can be integrated via Modbus communications protocol to AERCO’s multiple boiler management system (BMS) or a facilitywide Energy Management or Building Automation System. Natural Gas or Dual Fuel (Propane) 15:1 Turndown Ratio (7%) Oxygen Level (O2) Monitoring Standard Stainless Steel Fire Tube heat exchanger Capable of variable primary flow Installations NOx Emissions 20 ppm or less @ all firing rates Compact Footprint (79”H x 34”W x 108”D) Precise Temperature Control Ducted Combustion Air Capable Easy Open Access for Service Acceptable vent materials AL29-4C Reliable Quiet Operation Controls Options • Constant Setpoint • Indoor/ Outdoor Reset • Remote Setpoint •

 Open the catalog to page 1
BMK6000-2

RATINGS AND DIMENSIONS: Model AHRI Certified Weight Weight Shipping (dry) (wet) lbs. Weight lbs. 3,000 SPECIFICATIONS: ASME Working Pressure………………… 80 PSIG or 150 PSIG Electrical Options……………………………… 208/3/60 30 AMP ……………………………………………………460/3/60 15 AMP Gas Requirements: Natural Gas FM Gas Train ……………………… 14” W.C. Min. @ Full Load DBB (IRI) Gas Train………………… 14” W.C. Min. @ Full Load Dual Fuel FM Gas Train - Nat Gas……………… 14” W.C. Min. @ Full Fire FM Gas Train - Propane……………… 14” W.C. Min. @ Full Fire Water Connections …………………6” Flanged 150lb ANSI Vent/ Air Intake Connections…………………… 14 Inch Communications...

 Open the catalog to page 2

All AERCO International catalogs and technical brochures

  1. AM Series

    12  Pages

  2. C - MORE

    4  Pages

  3. BMK-SERIES

    4  Pages

  4. Modulex EXT

    4  Pages

  5. Esteem 399

    2  Pages

Related Searches
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.