More than 30 years expertise in Hygienic air treatment Reliability and performance Since 1987, ATA has demonstrated trustworthy expertise in the field of air treatment for hospital and industrial environments. Our designing activities are geared towards innovation as a strategic driver. ATA creates reliable hygiene products, developed by a design office with more than twenty years of experience. We also offer a large number of services to our partners: Audit, training and maintenance contract, in order to closely monitor market developments. APR APPLICATION FIELDS Healthcare establishments Micro-electronic...
Open the catalog to page 2CLINICAIR RANGE CLINICAIR® hygienic air handling units are developed to handle and guarantee the air quality conditions with precision and continuity. They are designed to achieve high targets of particle decontamination, bacteriological class, temperature, hygrometry and pressure in a place where contamination management is a major issue. Our CLINICAIR® cabinets are vertical, with reduced floor space. ATA offer consists of 3 ranges, including more than 100 models that operate in partial air recycling or 100% fresh air. Duct connections can be placed on the top, bottom, front, side. Sound traps...
Open the catalog to page 3CLINICAIR® 1b is a plug & play solution It meets the most exigent requirements for installation inside an operating room. Particularly effective in the fight against nosocomial infections, the effectiveness of CLINICAIR® 1b is obtained thanks to the combined actions of the Bioxigen® bacteriological decontamination system and HEPA filtration (H14 according to the EN 1822 standard, filtering capacity of 99.995% on particles up to 0.3 microns MPPS). ATA hygienic Clinicair allows to obtain a fast particle and bacteriological decontamination kinetics. The PCO5 monitoring system allows permanent control...
Open the catalog to page 6CLINICAIR 1B DETAILED DESCRIPTION BLOWING PLENUM (OPTION) BIOXIGEN® DECONTAMINATION SYSTEM Bioxigen® bacteriological decontamination system, with bactericidal, fungicidal effects on living particles. • Three-phase power supply: 400V N + T 50Hz. • The electrical box includes : - Contactors and thermal protections for power units. - Microprocessor regulation and control module with LCD display • Control by PCO5 automaton with “energy saving” programming. AIR SUPPLY FILTRATION H14 filtration with plenum, F9 without plenum (low pressure drop filter made of polypropylene). AIR INTAKE PREFILTRATION...
Open the catalog to page 7The CLINICAIR® 3 range meets the most important requirements of hyper-aseptic environments and offers a flow range of 1000 to 20,000 m3 / h and available pressures up to 1500Pa (See Technical Specifications). Specifications the models are available with chilled water or direct expansion coils for cooling and hot water or electric coils for heating The CLINICAIR® 3 range offers innovative solutions dedicated to air treatment and air conditioning in operating theaters and other high-risk areas within the hospital. It meets particularly demanding standards: NFS 90-351 April 2013 and EN 1886 and...
Open the catalog to page 8The CLINICAIR® air handling unit can be installed in private medical, surgery, obstetrics clinics, private and public hospitals. It’s 100% designed to be installed within “risk areas”: Hyper aseptic operating theater. Angiographic intervention • Operating theaters, • Risk 4/3/2 operating rooms, • resuscitation services, • hemodialysis services, • intensive care units in cardiology, • induction rooms, • MRI rooms, • coronary angiography rooms, • tomography, • angiography, • endoscopy rooms, • ophthalmic laser, • delivery rooms, • post-intervention care rooms, • cytotoxic productions, • cell therapy...
Open the catalog to page 9CLINICAIR 3 DETAILED DESCRIPTION FRAME AND CASING • One-piece frame, made of 40 mm aluminum profiles assembled with non-combustible nylon gaskets • “Double skin” panels in 15 / 10th - 8 / 10th steel with high density glass wool (40 kg / m3) providing thermal and sound insulation. • Panel closure system by high compression self-locking system • Soundproofed RAL 9010 satin panels on 3 or 4 sides with soundproofing foam. • Removable condensate pan for cleaning, made of AISI 316L stainless steel with removable rigid siphon. • Rear panel made of AISI 316L stainless steel, with diamond tip shape. •...
Open the catalog to page 103 VENTILATION • Variable speed drive to maintain a constant air flow depending on the clogging of the filters. • Low energy consumption single reaction freewheel motor fan (IE4). • EC or AC ventilator type (freewheel) AIR SUPPLY FILTRATION • F9/H13/H14 filtration ELECTRICAL BOX AND REGULATION • Three-phase power supply: 400V N + E 50Hz • The electrical box includes: - Contactors and thermal protections for power units. - Regulation and control module by microprocessor with display. - PCO5 (Carel) or others on request. - 3, 4 or 5 probes depending on the models (recycling or all new air) and the...
Open the catalog to page 11The CLINICAIR® 4 is a compact hygiene cabinet, ready to be connected, integrating all the components necessary for the treatment of the air, and for the control of temperature and hygrometry. It can be installed either in a technical room or outside the building, thus allowing a substantial saving in the costs of installation, operation and maintenance. CLINICAIR® 4 range offers innovative solutions dedicated to air treatment and air conditioning in operating theaters and other high-risk areas within the hospital in compliance with the requirements of standard NFS 90-351 April 2013, EN 1886 and...
Open the catalog to page 12Hopital Robert Debre (75) - bone marrow transplant center In private MCO clinics, private hospitals and Public hospitals, CLINICAIR® air handling unit equips 100% of departments classified as “risk areas”: • Operating Theaters, • Risk 4/3/2 operating rooms, • resuscitation services, • hemodialysis services, • intensive care units in cardiology, • induction rooms, • MRI rooms, • coronary angiography rooms, • tomography, • angiography, • endoscopy rooms, • ophthalmic laser, • delivery rooms, • post-intervention care rooms, • cytotoxic productions, • cell therapy laboratories, • hospital sterilizations,...