video corpo

TotalAlert Infinity HTM/ISO Specification Sheet
5Pages

{{requestButtons}}

Catalog excerpts

TotalAlert Infinity HTM/ISO Specification Sheet - 1

TotalAlert Infinity™ Medical Gas Notification System MEDICAL GAS NOTIFICATION SYSTEM SPECIFICATION Medical Gas Notification System The TotalAlert Infinity™ medical gas notification system provides central and area alarm signals as required by the latest edition of HTM02-01. The medical gas notification system shall fully comply with the requirements of HTM 02-01, BS EN 60601-1-2 and BS EN ISO 7396-1. The Right Instruction The medical gas notification system shall allow: • Set up customised instructions for each alarm signal, to appear on the screen when the signal is in alarm. • Create custom instructions with the touch screen interface on the alarm panel LCD. • Incorporate user-defined instructions into an emergency response plan by the facility. Panel Functionality • Central, Zone, and Combination medical gas notification systems shall have an 8” touch screen LCD display. Central Alarm Panel (up to 20 BeaconMedaes Line Contact Monitoring signals.) • Configuration of the medical gas notification system shall be done via build-in touch-screen Human-Machine Interface (HMI), no additional tools shall be required. • Duplication (cloning) of the configuration should be foreseen e.g. by using removable memory board. Remote Ethernet monitoring and secured configuration shall be foreseen without additional software. • A Green NORMAL condition on the home screen shows that there are no alarms active. • The home page includes a location/area served badge for the alarm panel, customisable with the keyboard feature of the touch screen during the set up process. • LCD display contains an adjustable background with many colour/ brightness options. • LCD display backlight includes a “sleep mode” option via motion sensor to preserve screen life, adjustable from 5 to 60 minutes. By default, the alarm sleep mode option is not active and the backlight remains on all of the time. If option is active and an alarm occurs during “sleep mode”, the backlight turns on and remains on during the alarm condition. Combination alarm can monitor up to 20 BeaconMedaes Line Contact Monitoring signals and up to 6 digital gas sensors. • A full diagnostic self-test of the alarm tests the alarm signals (Green, Yellow, and Red), the LED indicators on the front panel, the audible horn, and displays all of the alarm set points. Initiate test with the touchscreen controls. Antimicrobial Additive User accessible overlay material on the front panel shall include a silver antimicrobial additive for inherent antimicrobial protection. Efficiency of the additive according to ISO 22196 shall be >99% for sample of species such as E coli and MRSA. Ethernet Connectivity with Embedded Web Page • A built-in web server in each panel allows a remote operator to display the alarm’s web page and view alarm signals, pressures, and other networked devices. • Ethernet communication is compatible with BeaconMedaes TotalAlert Embedded source equipment, TotalAlert Embedded manifolds, and TotalAlert alarm panels. Zone Alarm Panel (up to 8 gases) • The panel’s web page contains links to all other TotalAlert devices on BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● gbn.info@beaconmedaes.com Constructionline Reg No. 75463 ● CHA

Open the catalog to page 1
TotalAlert Infinity HTM/ISO Specification Sheet - 2

the network, including other alarm panels and source equipment. • Electronic notification is available through e-mail/text messaging. • Accessible through any SMTP gateway. • Allows for remote alerts of alarm conditions. History Log • Event log accessible on LCD display records all alarms and panel activity, displays most recent 100 events. • WARNING LED alerts the user to warnings and communication issues which are not alarm causing conditions. • Audible SPEAKER produces a minimum sound pressure of 58 dBA at a distance of 1m. • MUTE button indicator LED flashes red during an alarm...

Open the catalog to page 2
TotalAlert Infinity HTM/ISO Specification Sheet - 3

• Gas specific digital gas sensor contains a transducer capable of providing factory calibrated signals to the alarm panel. Source alarm signal with custom, alarm specific instruction • Remotely installed sensors may be located up to 1,524 m (5,000 feet) from the alarm panel. • Pipeline connections are 1/4” BSPP threaded connection with sealing washer. • Digital gas sensors include a “heartbeat” flashing green LED light to designate that sensor is functioning correctly. Zone Alarm Panel Configuration • Zone alarm panel monitors 1 to 8 digital gas sensor modules, installed remotely. •...

Open the catalog to page 3
TotalAlert Infinity HTM/ISO Specification Sheet - 4

TotalAlert Infinity™ Alarm Models Product number BeaconMed*s • Telford Crescent, Staveley, Derbyshire S43 3PF • Tel: +44 (0) 1246 474 242 • Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) • Company VAT Reg No. 598612590 • www.beaconmedaes.com • gbn.info@beaconmedaes.com Constructionline Reg No. 75463 • CHAS accredited contractor • SAFEcontractor Reg No. N00184450

Open the catalog to page 4
TotalAlert Infinity HTM/ISO Specification Sheet - 5

In an effort to continuously improve our products, 4107951155.01 the right is reserved to change the specification of the 2212020128 items described herein at any time. Please contact us for further information and up to date specifications. 08/10/17 Page 5 of 5 TotalAlert Infinity™ Alarm Dimensions 16.4 mm 202.0 mm Finished Wall Concealed Installation Dimensions Front Panel Hinged For Internal Access Surface Installation Dimensions BeaconMedæs Telford Crescent, Staveley, Derbyshire Patent Pending © BeaconMedæs 22-07-

Open the catalog to page 5

All BeaconMedaes catalogs and technical brochures

  1. Local alarm

    4 Pages

  2. Magnis MSV

    2 Pages

  3. mVAC

    12 Pages

Archived catalogs