ActivAIR™ 36CB

Product catalog summary
Overview: The document details the Carrier Corporation's 36CBAL and CBAJ Series Active Chilled Beams, designed for applications requiring individual temperature control with precise ventilation airflow and options for sensible cooling and heating.

Active Chilled Beam Systems: These systems use primary air at static pressures of 0.2 to 0.8 in. wg, distributed through aerodynamic nozzles into a mixing chamber. This induces room air across a coil for cooling or heating, with mixed air discharged through a grille using the Coanda effect. The system is efficient, quiet, and reduces maintenance and energy costs by eliminating filters and fan motors.

36CB Series Models: The 36CBAL (2-way discharge) and 36CBAJ (1-way discharge) models are ceiling-mounted units available in sizes of 2x2 ft, 2x4 ft, and 2x6 ft, suitable for office spaces, labs, and dormitories, handling sensible cooling loads without condensate piping.

Features and Benefits: Units include pressure taps for airflow balancing, mounting brackets for easy installation, and optional insulation to prevent condensation. They are designed for low noise operation with an acoustically insulated return air chamber.

Model Number Nomenclature: The document provides a breakdown of model numbers, detailing unit size, nozzle type, primary air configuration, piping configurations, and optional features like filters and grille finishes.

Factory-Installed Options: Options include various induction nozzle sizes, 2-pipe or 4-pipe coil configurations, and different grille colors. Optional insulation is recommended for primary air temperatures below 55°F.

Application Data: Chilled beam systems are ideal for applications requiring individual temperature control, with a maximum cooling capacity of 25 to 30 Btuh per sq ft. They reduce fan power requirements and space needed for air-handling equipment, and can be configured with double water use, secondary water loops, or separate air and water systems.

Guide Specifications: Specifications include system description, quality assurance standards, and equipment details. Units are designed for flush mounting in false ceilings and include hanging brackets for installation.

Unit Specifications:
1. Equipped with a round low-velocity pressure primary inlet transition, air plenum, air induction nozzle plate, chilled/hot water coil, and supply/return piping connections. Features a one or two-slot supply opening with a return air grille for Coanda effect room air distribution.
2. Latent conditioning is managed by a dedicated outdoor air unit with exhaust air humidity sensors, maintaining building humidity below 50% relative humidity.
3. A built-in pressure tap on the primary air inlet allows for air static pressure measurement and balancing.

Unit Construction:
1. Constructed from 20-gauge galvanized G90 sheet metal for uniform air distribution with low noise.
2. Slot supply openings provide linear one-way or 2-way Coanda effect air distribution.
3. The grille return section is perforated and hinged for tool-free access.

Induction Nozzles: Made from DuPont Hytrel 4069 Engineering Polymers, designed for efficient airflow and minimal dirt build-up, tested under UL94 and UL746 standards.

Water Coil Assembly:
1. Coils are made of aluminum fins and copper tubes, factory leak tested at 350 psig water.
2. Coils are a single flat plate assembly with no interconnecting joints, minimizing leakage.
3. Includes a two-row copper tube and aluminum fins for cooling and heating, with control valves supplied by the Automatic Temperature Control Contractor.

Grille Finish: The standard finish is baked-on acrylic enamel.

Optional Exterior Insulation: Insulation is provided for units with primary air temperatures below 55°F, using closed-cell elastomeric foam that meets various ASTM and NFPA standards.

Optional Lint Filters:
1. Lint filters are available as washable or disposable types.
2. Washable filters have an aluminum frame with woven nylon mesh media.
3. Disposable filters have fiberglass media and comply with UL 217V.

Note: Manufacturer reserves the right to change specifications or designs without notice.
See more

Catalog excerpts

ActivAIR™ 36CB-1

Product Data 36CBAL,CBAJ Series Active Chilled Beams 8 to 180 cfm

 Open the catalog to page 1
ActivAIR™ 36CB-2

Features/Benefits Chilled beam systems are suitable for use in sensible cooling load applications where individual temperature control is required. Active chilled beam units offer: • Precise control of ventilation airflow • Sensible cooling and heating options Active chilled beam systems An active chilled beam takes a source of primary air at an inlet static pressure ranging from 0.2 to 0.8 in. wg. It distributes this air through a bank of specially designed aerodynamic nozzles and discharges the air at a high velocity into a mixing chamber. This creates a differential pressure which enables...

 Open the catalog to page 2
ActivAIR™ 36CB-3

36CB A L C B 2 EGOY GAYYY 36CB - Chilled Beam Design Revision A - Current Design Product Style J - 1-Way Linear Slot L - 2-Way Linear Slot Unit Size - Footprint (in.) B - 48 X 24 C - 24 X 24 E - 72x24 F - 96 x 24 (36CBAL) (ETO) Nozzle Type A - 1-Row, 24-Size B - 2-Row, 24-Size C - 1-Row, 31-Size D - 2-Row, 31-Size E - 1-Row, 38-Size F - 2-Row, 38-Size G - 1-Row, 18-Size H - 2-Row, 18-Size System Type 2 - 2-Pipe, 2-Row Coil 5 - 4-Pipe, 2-Row Coil with Split Circuiting Primary Air Configuration E - End C - Center Piping Configurations B - Right Hand (2-Pipe) C - Left Hand (2-Pipe) G - Same End...

 Open the catalog to page 3
ActivAIR™ 36CB-4

Factory-installed options Factory-installed options Induction nozzles are available in various sizes to match capacity requirements. Coils are available in 2-pipe or 4-pipe configurations. Grilles are available in various colors with perforated return and slot supply. The grille is hinged with easy access latches. Face and trim of the grille are painted standard white color. Optional insulation on the unit exterior (inlcuding the primary air tube) is recommended when the primary air temperature supplied to the unit is below 55°F. The optional insulation used is Armacell Model AP sheet insulation....

 Open the catalog to page 4
ActivAIR™ 36CB-5

36CBAL, 2-PIPE, SIZE 02 UNIT DIMENSIONS - 0 PRIMARY AIR END CONNECTION HANGER BRACKET - LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

 Open the catalog to page 5
ActivAIR™ 36CB-6

Dimensions (cont) 36CBAL, 2-PIPE, SIZE 04 UNIT DIMENSIONS Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicate

 Open the catalog to page 6
ActivAIR™ 36CB-7

36CBAL, 2-PIPE, SIZE 06 UNIT DIMENSIONS HANGER BRACKET- LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

 Open the catalog to page 7
ActivAIR™ 36CB-8

Dimensions (cont) 36CBAL, 4-PIPE, SIZE 02 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicate

 Open the catalog to page 8
ActivAIR™ 36CB-9

36CBAL, 4-PIPE, SIZE 04 UNIT DIMENSIONS -6"0 PRIMARY AIR CONNECTION 1/2" COPPER CWS HANGER BRACKET LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

 Open the catalog to page 9
ActivAIR™ 36CB-10

1/2" COPPER CWS-HANGER BRACKET- LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

 Open the catalog to page 10
ActivAIR™ 36CB-11

36CBAJ, 2-PIPE, SIZE 02 UNIT DIMENSIONS 6"0 PRIMARY AIR END CONNECTION PRESSURE TAP — Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

 Open the catalog to page 11
ActivAIR™ 36CB-12

Dimensions (cont) 36CBAJ, 2-PIPE, SIZE 04 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated

 Open the catalog to page 12
ActivAIR™ 36CB-13

36CBAJ, 2-PIPE, SIZE 06 UNIT DIMENSIONS PRESSURE TAP-1 6"0 PRIMARY AIR END CONNECTION 1/2 71.75 " COPPER CWS HANGER BRACKET 1/2" COPPER HWR 6"0 PRIMARY AIR CONNECTION 1/2" COPPER CWR Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

 Open the catalog to page 13
ActivAIR™ 36CB-14

Dimensions (cont) 36CBAJ, 4-PIPE, SIZE 02 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated

 Open the catalog to page 14
ActivAIR™ 36CB-15

36CBAJ, 4-PIPE, SIZE 04 UNIT DIMENSIONS Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

 Open the catalog to page 15
ActivAIR™ 36CB-16

Dimensions (cont) 36CBAJ, 4-PIPE, SIZE 06 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated

 Open the catalog to page 16
ActivAIR™ 36CB-17

Selection procedure Refer to Carrier Electronic Selection Program or contact your Carrier representative to determine unit size for your application. Application data Systems with chilled beams are suitable for use in sensible cooling load applications and/or where there is a requirement for individual temperature control. In offices with normal room heights, the maximum cooling capacity is 25 to 30 Btuh per sq ft of floor area. The limit is set by the maximum permissible velocity in the occupied zone, therefore high room heights can provide the opportunity for supplying a greater cooling effect....

 Open the catalog to page 17
ActivAIR™ 36CB-18

Application data (cont) DOUBLE USE OF THE WATER COOLING TOWER MIXING VALVE 58 F WATER 57 F WATER CHILLED BEAMS WATER COOLED CHILLERS SECONDARY WATER LOOP Dehumidifier Heat Pipe 95 F Air 45 F Water T Stat 45 F Water Heat Exchanger

 Open the catalog to page 18
ActivAIR™ 36CB-19

SEPARATE SYSTEMS ALTOGETHER Individual Zone Control 55 F Air T Stat Improved COP with warmer water

 Open the catalog to page 19
ActivAIR™ 36CB-20

Guide specifications Active Chilled Beams HVAC Guide Specifications Size Range: 2, 4, and 6 ft Carrier Model Number: 36CBAL,J Part 1 — General 1.01 SYSTEM DESCRIPTION A. Integrated chilled beam system for ventilation, cooling, and heating. B. Chilled beam unit shall be constant volume primary airflow unit designed to induce a secondary airflow within the conditioned space using the primary conditioned air supply. Capacities and characteristics as listed in the schedule and the guide specifications that follow. 1.02 QUALITY ASSURANCE A. Unit coils shall be tested in general accordance with the...

 Open the catalog to page 20

All Carrier| Commercial Systems North America catalogs and technical brochures

  1. Axis™

    2  Pages

Archived catalogs

  1. 50ZPB

    4  Pages

  2. AHUBuilder

    2  Pages

  3. 39CC

    2  Pages

  4. 48XL-A

    30  Pages

  5. 48PM CENTURION?

    64  Pages

  6. 48PG CENTURION?

    107  Pages

  7. OMNIZONE?

    80  Pages

  8. 39L AERO®

    52  Pages

  9. 39S

    36  Pages

  10. 30RB AQUASNAP®

    92  Pages

  11. AQUAFORCE® 30XA

    150  Pages

  12. 16TJ

    32  Pages

  13. 39M AERO®

    110  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.