ActivAIR™ 36CB
24Pages

{{requestButtons}}

Catalog excerpts

ActivAIR™ 36CB - 1

Product Data 36CBAL,CBAJ Series Active Chilled Beams 8 to 180 cfm

Open the catalog to page 1
ActivAIR™ 36CB - 2

Features/Benefits Chilled beam systems are suitable for use in sensible cooling load applications where individual temperature control is required. Active chilled beam units offer: • Precise control of ventilation airflow • Sensible cooling and heating options Active chilled beam systems An active chilled beam takes a source of primary air at an inlet static pressure ranging from 0.2 to 0.8 in. wg. It distributes this air through a bank of specially designed aerodynamic nozzles and discharges the air at a high velocity into a mixing chamber. This creates a differential pressure which...

Open the catalog to page 2
ActivAIR™ 36CB - 3

36CB A L C B 2 EGOY GAYYY 36CB - Chilled Beam Design Revision A - Current Design Product Style J - 1-Way Linear Slot L - 2-Way Linear Slot Unit Size - Footprint (in.) B - 48 X 24 C - 24 X 24 E - 72x24 F - 96 x 24 (36CBAL) (ETO) Nozzle Type A - 1-Row, 24-Size B - 2-Row, 24-Size C - 1-Row, 31-Size D - 2-Row, 31-Size E - 1-Row, 38-Size F - 2-Row, 38-Size G - 1-Row, 18-Size H - 2-Row, 18-Size System Type 2 - 2-Pipe, 2-Row Coil 5 - 4-Pipe, 2-Row Coil with Split Circuiting Primary Air Configuration E - End C - Center Piping Configurations B - Right Hand (2-Pipe) C - Left Hand (2-Pipe) G - Same...

Open the catalog to page 3
ActivAIR™ 36CB - 4

Factory-installed options Factory-installed options Induction nozzles are available in various sizes to match capacity requirements. Coils are available in 2-pipe or 4-pipe configurations. Grilles are available in various colors with perforated return and slot supply. The grille is hinged with easy access latches. Face and trim of the grille are painted standard white color. Optional insulation on the unit exterior (inlcuding the primary air tube) is recommended when the primary air temperature supplied to the unit is below 55°F. The optional insulation used is Armacell Model AP sheet...

Open the catalog to page 4
ActivAIR™ 36CB - 5

36CBAL, 2-PIPE, SIZE 02 UNIT DIMENSIONS - 0 PRIMARY AIR END CONNECTION HANGER BRACKET - LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

Open the catalog to page 5
ActivAIR™ 36CB - 6

Dimensions (cont) 36CBAL, 2-PIPE, SIZE 04 UNIT DIMENSIONS Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicate

Open the catalog to page 6
ActivAIR™ 36CB - 7

36CBAL, 2-PIPE, SIZE 06 UNIT DIMENSIONS HANGER BRACKET- LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

Open the catalog to page 7
ActivAIR™ 36CB - 8

Dimensions (cont) 36CBAL, 4-PIPE, SIZE 02 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicate

Open the catalog to page 8
ActivAIR™ 36CB - 9

36CBAL, 4-PIPE, SIZE 04 UNIT DIMENSIONS -6"0 PRIMARY AIR CONNECTION 1/2" COPPER CWS HANGER BRACKET LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

Open the catalog to page 9
ActivAIR™ 36CB - 10

1/2" COPPER CWS-HANGER BRACKET- LEGEND CWR — Chilled Water Return CWS — Chilled Water Supply HWR — Heated Water Return HWS — Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

Open the catalog to page 10
ActivAIR™ 36CB - 11

36CBAJ, 2-PIPE, SIZE 02 UNIT DIMENSIONS 6"0 PRIMARY AIR END CONNECTION PRESSURE TAP — Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

Open the catalog to page 11
ActivAIR™ 36CB - 12

Dimensions (cont) 36CBAJ, 2-PIPE, SIZE 04 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated

Open the catalog to page 12
ActivAIR™ 36CB - 13

36CBAJ, 2-PIPE, SIZE 06 UNIT DIMENSIONS PRESSURE TAP-1 6"0 PRIMARY AIR END CONNECTION 1/2 71.75 " COPPER CWS HANGER BRACKET 1/2" COPPER HWR 6"0 PRIMARY AIR CONNECTION 1/2" COPPER CWR Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

Open the catalog to page 13
ActivAIR™ 36CB - 14

Dimensions (cont) 36CBAJ, 4-PIPE, SIZE 02 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated

Open the catalog to page 14
ActivAIR™ 36CB - 15

36CBAJ, 4-PIPE, SIZE 04 UNIT DIMENSIONS Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated.

Open the catalog to page 15
ActivAIR™ 36CB - 16

Dimensions (cont) 36CBAJ, 4-PIPE, SIZE 06 UNIT DIMENSIONS PRIMARY AIR END CONNECTION Chilled Water Return Chilled Water Supply Heated Water Return Heated Water Supply NOTE: Dimensions shown in inches unless otherwise indicated

Open the catalog to page 16
ActivAIR™ 36CB - 17

Selection procedure Refer to Carrier Electronic Selection Program or contact your Carrier representative to determine unit size for your application. Application data Systems with chilled beams are suitable for use in sensible cooling load applications and/or where there is a requirement for individual temperature control. In offices with normal room heights, the maximum cooling capacity is 25 to 30 Btuh per sq ft of floor area. The limit is set by the maximum permissible velocity in the occupied zone, therefore high room heights can provide the opportunity for supplying a greater cooling...

Open the catalog to page 17
ActivAIR™ 36CB - 18

Application data (cont) DOUBLE USE OF THE WATER COOLING TOWER MIXING VALVE 58 F WATER 57 F WATER CHILLED BEAMS WATER COOLED CHILLERS SECONDARY WATER LOOP Dehumidifier Heat Pipe 95 F Air 45 F Water T Stat 45 F Water Heat Exchanger

Open the catalog to page 18
ActivAIR™ 36CB - 19

SEPARATE SYSTEMS ALTOGETHER Individual Zone Control 55 F Air T Stat Improved COP with warmer water

Open the catalog to page 19
ActivAIR™ 36CB - 20

Guide specifications Active Chilled Beams HVAC Guide Specifications Size Range: 2, 4, and 6 ft Carrier Model Number: 36CBAL,J Part 1 — General 1.01 SYSTEM DESCRIPTION A. Integrated chilled beam system for ventilation, cooling, and heating. B. Chilled beam unit shall be constant volume primary airflow unit designed to induce a secondary airflow within the conditioned space using the primary conditioned air supply. Capacities and characteristics as listed in the schedule and the guide specifications that follow. 1.02 QUALITY ASSURANCE A. Unit coils shall be tested in general accordance with...

Open the catalog to page 20

All Carrier| Commercial Systems North America catalogs and technical brochures

  1. Axis™

    2 Pages

  2. AHUBuilder

    2 Pages

  3. 50ZPB

    4 Pages

  4. 39CC

    2 Pages

  5. 48PG CENTURION?

    107 Pages

  6. 48XL-A

    30 Pages

  7. OMNIZONE?

    80 Pages

  8. 16TJ

    32 Pages

  9. 39S

    36 Pages

  10. 39L AERO®

    52 Pages

  11. 39M AERO®

    110 Pages

Archived catalogs