1. Catalogs
  2. DIB Radioprotection
  3. Radiation Protection SLIDING DOOR For Radiation Therapy room

Radiation Protection SLIDING DOOR For Radiation Therapy room

Radiation Protection SLIDING DOOR For Radiation Therapy room

Radiation Protection SLIDING DOOR For Radiation Therapy room

Product catalog summary
Overview
DIB specializes in designing, manufacturing, and installing radiation protection solutions such as leaded and neutronic doors, wall shielding, partitions, cabinets, and interlock transfer systems for radiation therapies and nuclear medicine installations worldwide. The company emphasizes safety and customization to meet specific client needs.

Radiation Protection Sliding Door for Radiotherapy Rooms
  • Application: Designed for radiotherapy rooms with a maze configuration.
  • Shielding Options: Tailored according to room configuration and Linac type, using lead and/or steel (30mm to 100mm) and paraffin or polyethylene with or without boron (0mm to 400mm).
  • Dimensions: Free passage width ranges from 0.9m to 1.6m, and height from 2.0m to 2.3m. Custom dimensions available upon request.
  • Leaf Weight: Ranges from 1000 to 10000 kg.

Safety Features
  • Heavy Door Safeties (EN 13241-1): Includes emergency stops, cell beams, contact strips, and orange flashing lights on both sides of the door.
  • Radiation Safeties: Equipped with dry contact switches to ensure the door is closed before accelerator operation. Optional sound bell and "Last Man Out" button available.
  • Mechanical Safety: Mechanism declutches and stops if unusual opening or closing times are detected.

Door Control
  • Features include opening, half-opening, and closing controls, with a three-position key button for automatic, manual, and locked positions. Manual mode is easily accessible with a declutch button inside. Remote control option available.

Additional Options
  • Fixed frame or partition around the passage door with alternative materials like lead, steel, paraffin, or polyethylene.
  • Partitions to conceal the door when open and various finishing options including painted steel, stainless steel, and wooden finishes.

Door Finishing and Maintenance
  • Features include silent and robust mechanisms, quick opening/closing times starting at 10 seconds, and easy manual operation with a crank.
  • Mechanism located outside the bunker for easy access and maintenance.

Contact Information
DIB Production, 2 rue Joseph Jacquard, 21800 Sennecey-lès-Dijon, France. Phone: +33 (0)3 80 59 61 40, Email: [email protected], Website: DIB Production
See more

Catalog excerpts

Radiation Protection SLIDING DOOR For Radiation Therapy room-1

Radiation Protection SLIDING DOOR For Radiation Therapy room Application : Radiotherapy room with maze Since 30 years, our engineers and technicians design, manufacture and install radiation protection leaded and neutronic doors, wall shielding, partitions, cabinets and interlock transfer systems for Radiation Therapies and Nuclear Medicine installations worldwide. Whatever the size, the weight or the location DIB teams do their best to satisfy your requirements and to bring to you, your personnel and your customers a safe environment. SHIELDING: According to room configuration and Linac type Lead and/or Steel: 30mm to 100 mm Paraffin or Polyethylene, with or without boron: 0 mm à 400 mm DIMENSIONS For free passage: width 0,9m to 1, 60 m, height 2,0m to 2,3m Other dimensions: contact us LEAF WEIGHT: 1000 to 10000 kg Tailor Made solutions Our customers includ

 Open the catalog to page 1
Radiation Protection SLIDING DOOR For Radiation Therapy room-2

SAFETY – REABILITY – SPEED -- SILENCE – EASY MAINTENANCE • • • • • • • Door and mechanism located outside bunker, access always possible, Silent and Robust mechanism with high level torque, Opening/Closing time starting at 10 s, Electromagnetic clutch - adjustable torque due to a potentiometer, Start and Stop go through a low speed, which enables a flexible functioning and a precise stop, Door hanged on an upper rail through two rollers, floor guide outside the passage Easy manual opening opening and closing with a crank. HEAVY DOOR SAFETIES EN 13241-1 • • • • Emergency stop on both sides of the...

 Open the catalog to page 2

All DIB Radioprotection catalogs and technical brochures

  1. X-ray Bunker

    3  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.