Chilled beam Flexicool® IQID
5Pages

{{requestButtons}}

Catalog excerpts

Chilled beam Flexicool® IQID - 1

Chilled beam Flexicool® IQID Chilled beam Flexicool® IQID Functions • FPC • High air flow • Controls • Lighting • Comfort control • Heating • Sprinkler The chilled beam Flexicool® IQID is an integrated system for ventilation, cooling and heating, fulfilling most needs for indoor climate. The IQID chilled beam is a very flexible chilled beam that is available as a basic model, but can also be equipped with a number of functions to provide a multifunctional chilled beam. The following functions are available for IQID: heat, comfort setting, Flow Pattern Control (FPC air deflector), function for high air flow, control and regulation equipment, lighting and provision for a sprinkler system. These various functions are described in separate parts in the catalogue. IQID has a covered upper side and is intended for flush-mounting in false ceilings and has dimensions adapted to a false ceiling module of 600 mm Quick Selection Product Facts • IQID chilled beam for flushmounting in false ceilings • Very flexible - available in a wide range of executions from basic to multifunctional • Adapted for standard 600 mm false ceiling module • Fastening brackets for rapid and simple installation - lift up - snap in place • Available with the following functions: heating, comfort control, Flow Pattern Control (FPC air deflector), function for high air flow, control equipment, lighting and provision for a sprinkler system Product code example Covered chilled beam IQID-240-1-1-01, standard. The diagram shows the approximate cooling effect P tot in W with water flow qw = 0,05 l/s , temperature difference between room air and supply air Δt= 8 °C , pressure drop 70 Pa on the air side and max. sound pressure level L A10 = 30 dB(A). Fläkt Woods Specifications are subject of alteration without further notice.

Open the catalog to page 1
Chilled beam Flexicool® IQID - 2

Chilled beam Flexicool® IQID Technical data for cooling and heating effect Cooling effect for two-way chilled beam at static pressure drop 70 Pa on the air side Beam length = 1.2 m (Coil length = 0.9 m) Water flow, q w = 0.05 l/s Pressure drop water, Δp w = 1.8 kPa q l , l/s 5 10 15 This means that the table value concerned can be increased by 10 - 20 %. The chilled beam can be supplied with a special construction for higher air flows than listed in these tables. Heating effect for two-way chilled beam IQID at static pressure drop 70 Pa on the air side Heating effects can be found in...

Open the catalog to page 2
Chilled beam Flexicool® IQID - 3

Chilled beam Flexicool® IQID Technical data for other flow patterns, sound data Technical data for flow patterns other than two- Beams with two-way air distribution utilize the coil in full, which is not the case in one-way distribution or middle positions. This effect factor can be found in the table below For a particular beam and supply air flow, the obtained effect factor is multiplied by the value given in the effect tables on the previous page. Type of Beam Max. supply Effect distribution length, m airflow, l/s factor Beam of length = 2,4 m with one-way air distribution, air flow = 20...

Open the catalog to page 3
Chilled beam Flexicool® IQID - 4

Chilled beam Flexicool® IQID Female connection Male connection Water volume cooling = 0.50 1/m coil Water volume heating = 0.25 1/m coil Flakt Woods Specifications are subject of alteration without further notice.

Open the catalog to page 4
Chilled beam Flexicool® IQID - 5

Chilled beam Flexicool® IQID Description and product code Product code Main code Covered supply air beam, standard Set with 2 pcs. Length 500 mm. 2 sets QFAZ-12 per beam Connection alternative (b) 1 = Standard 2 = Extended casing, 600 mm, connection side (Not IQID-360) Corner unit Coil construction (c) 1 = Cooling 2 = Cooling with purging nipple 3 = Cooling and heating 4 = Cooling and heating with purging nipple Execution (bb) 01 = Standard 02 = Extended 600mm Comfort control (dd) 1) 01 = With Comfort control, 1 hole row 02 = With Comfort control, 1 hole row and FPC Installation (d) 1 =...

Open the catalog to page 5