Catalog excerpts
Flexicool® cassette chilled beam IQCA Flexicool® cassette chilled beam IQCA Functions • Coanda Safety Control • FPC • Comfort Control • Controls Flexicool® cassette chilled beam IQCA is an integrated system for ventilation and cooling fulfilling most needs for indoor climate. This cassette chilled beam is designed to manage high cooling effects that, because of good mixing with room air, provide comfort and low air velocities in the occupied zone. IQCA has the same unique function as other chilled beams from Fläkt Woods and is equipped with comfort control and has control equipment as accessory. The combination gives flexibility when dimensioning the indoor climate. IQCA cassette chilled beam is also equipped with Coanda Safety Control which guarantees adhesion of the air stream to the ceiling. This function is necessary in the area of low air flow to garantee a good indoor climate. IQCA has a covered upper side and is intended for flush-mounting in false ceilings and has dimensions adapted to a false ceiling module of 600 mm. Product Facts Quick Selection Cassette chilled beam IQCA-060-1-1-01 Cooling effect in W incl supply air • Cassette chilled beam for integrating in suspended ceiling • Available with the functions comfort control and control equipment. • Suited for standard 600 mm cealing module • Available in two lengths, 600 mm and 1200 mm Product code example Supply air flow, l/s The diagram shows the approximate cooling effect Ptot in W with water flow qw = 0,05 l/s , temperature difference between room air and supply air Δt = 10 °C . Temperature difference between mean water temperature and room temperature, Δt = 10 °C . Fläkt Woods Specifications are subject of alteration without further notice.
Open the catalog to page 1Flexicool® cassette chilled beam IQCA Cooling effects for IQCA-060 and IQCA-120 Cooling effect for four-way cassette IQCA-060 Cooling effect for four-way cassette IQCA-120 Static pressure 60 Pa on the air side Static pressure 60 Pa on the air side Water flow, q w = 0,05 l/s Pressure drop water, Δp w = 5,8 kPa Water flow, q w = 0,05 l/s Pressure drop water, Δp w = 10,1 kPa Static pressure 80 Pa on the air side Static pressure 80 Pa on the air side Water flow, q w = 0,05 l/s Pressure drop water, Δp w = 5,8 kPa Water flow, q w = 0,05 l/s Pressure drop water, Δp w = 10,1 kPa Static pressure 100...
Open the catalog to page 2Flexicool® cassette chilled beam IQCA Flow patterns, sound data, corrections, pressure drop Technical data for flow patterns other than four- Type of Distribution IQCA Min. supply Effect factor The effect factor is no longer valid as a calculating value when the supply air flow is below minimum. Two- and three-way distribution is recommended for a better flow pattern when the air flow is low. Alternatively use the Sound power level IQCA Correction K oct, dB Octave band, middle frequency (Hz) The sound power levels for each octave band are obtained by adding the sound pressure level T AIO /...
Open the catalog to page 3Flexicool® cassette chilled beam IQCA Operating weight: 20 kg (incl. cooling water) 20,1 kg (incl. cooling and heating water) Operating weight: 37,4 kg (incl. cooling water) 39,6 kg (incl. cooling and heating water) Flakt Woods Specifications are subject of alteration without further notice.
Open the catalog to page 4Flexicool® cassette chilled beam IQCA Operating weight: 20 kg (incl. cooling water) 20,1 kg (incl. cooling and heating water) Operating weight: 37,4 kg (incl. cooling water) 39,6 kg (incl. cooling and heating water) Flakt Woods Specifications are subject of alteration without further notice.
Open the catalog to page 5Flexicool® cassette chilled beam IQCA Product code, special units, accessories Construction and function Product code Cassette chilled beam IQCA is designed for ceiling mounting, and it is suited for standard 600 mm or 1200 mm ceiling modules, both in length and width, which means that it is flush with the ceiling surface. Main code Cassette chilled beam IQCA has the same unique function as other chilled beams from Fläkt Woods and is equipped with comfort control and has control equipment as accessory. Execution (b) 1 = Prepared for mounting bracket QFAZ-18-4 2 = Prepared for suspension rod...
Open the catalog to page 6All Fläkt Woods Group catalogs and technical brochures
-
HyPower-Geko
16 Pages
-
vQ STREAM
16 Pages
-
ATpicco
12 Pages
-
ReCOOLER HP
16 Pages
-
Ecodesign
8 Pages
-
diffuser range
8 Pages
-
ECONET ® PREMIUM
7 Pages
-
SEMCO
8 Pages
-
eQ ™ Air
202 Pages
-
EUMM Air conditioning unit Catalogue
245 Pages
-
Cooler and ReCooler
5 Pages
-
LVD Unit Heater, TEMPER
44 Pages
-
ATD Unit Heater
56 Pages
-
ControlMaster
4 Pages
-
Chilled beam Flexicool® IQID
5 Pages
-
Chilled beam Flexicool® IQIC
2 Pages
-
IPSUM Optimization System
16 Pages
-
Chilled beam iQ Star WEGA
13 Pages
-
Chilled Beam IQ Star STELLA
9 Pages
-
RoomMaster ABR unit
16 Pages
-
Air Handling Unit EU
203 Pages
-
Supply air unit VEKA
4 Pages
-
TapMaster Air Handling Unit
16 Pages
-
eQ Energy Solutions
4 Pages