MEDICAL CENTRAL GAS - 1

EDICAL CATALOGUE Global Central Gas Range

Open the catalog to page 1
MEDICAL CENTRAL GAS - 2

Sales office Sales representation Headquarters Production unit Stock point THE GCE BUSINESS GCE has almost 100 years of experience in the manufacture and supply of high pressure gas equipment. During this time the GCE product range has increased dramatically. Today´s product portfolio fits a large variety of applications, from simple pressure regulators and blowpipes for cutting and welding to highly sophisticated gas supply systems for the medical, electronic and analytical industries. GCE GROUP INCLUDES FOUR BUSINESS AREAS: • Cutting & Welding Technologies • Valves • Healthcare • Druva...

Open the catalog to page 2
MEDICAL CENTRAL GAS - 3

CONTENTS CONTACT PAGE GAS MANIFOLDS AND STABILIZERS . . . . . . . . . Gas Manifold MC25 . . . . . . . . . . . . . . . . . . . Gas Manifold MM40 - HP unit. . . . . . . . . . . . . Line Regulator . . . . . . . . . . . . . . . . . . . . . . Gas Manifold MM40 – Stabilizer . . . . . . . . . . . Gas Manifold MM90 - HP Unit (Fully Automatic) . Gas Manifold MM90 - HP Unit . . . . . . . . . . . . Gas Manifold MM90 - Stanby (Backup) . . . . . . . Gas Manifold Duplex (MC80) . . . . . . . . . . . . . Gas Manifold MC80 - Stabilizer . . . . . . . . . . . . Gas manifold MC150 - Stabilizer . . . . . . . ....

Open the catalog to page 3
MEDICAL CENTRAL GAS - 4

GG©druva HUNGARY GCE Hungaria Kft. II. Rakoczi Ferenc ut 68. H-2314 Halasztelek Phone: +36 (24) 521 200 Fax: +36 (24) 521 201 sales.hu@gcegroup.com MED ITALY GCE Mujelli spa Via F. lli Cervi, 11 37036 S. M. Buon Albergo (VR) Phone: +39 045 878 0 525 Fax: +39 045 878 0 750 sales.it@gcegroup.com SWEDEN Postal address: GCE Norden AB Box 21044 200 21 Malmo Visitors address: Kallvattengatan 9 212 23 Malmo Phone: +46-40-388300 Fax: +46-40-388353 sales.se@gcegroup.com ASIA CHINA GCE Gas Control Equipment Co., Ltd. No.4 Building, 318 Xiao Wan Road Fengxian District, Shanghai 201401 P.R....

Open the catalog to page 4
MEDICAL CENTRAL GAS - 5

MED GAS MANIFOLDS AND STABILIZERS GAS MANIFOLD MC25 The gas cylinder manifold MC25 has a capacity of 25 m3/h and is primarily intended for small and medium-sized hospitals. The gas cylinder pressure is regulated in two steps. The change-over between operating side and reserve side is made automatically without any differences in the operating pressure. The alarm signal comes from the pressure switches to the alarm unit. The alarm signals from the alarwm unit can be forwarded directly to a monitoring desk. Function control and service can be carried out without interruption in the gas...

Open the catalog to page 5
MEDICAL CENTRAL GAS - 6

MED FLOW CHARTS OF MANIFOLD MC25 PRESSURE CHARACTERISTIC

Open the catalog to page 6
MEDICAL CENTRAL GAS - 7

GOSdruva MED Manifold MM40 HP unit is an automatic manifold. It is working on the principal different pressure between the operation and reserve regulator. By the manual lever, the operator can decide which side will be the operational side and which will be the reserve side. When the operating side is empty, the manifold will without any action start to supply gas from the reserve side with the lower regulator pressure and fulfill! the requests to supply without interrupting the flow. MM40 HP unit manifolds together with a stabilizer should be used as second and third source of gas...

Open the catalog to page 7
MEDICAL CENTRAL GAS - 8

MED FLOW CHART OF MANIFOLD MM40 PRESSURE CHARACTERISTIC BASIC DIMENSIONS

Open the catalog to page 8
MEDICAL CENTRAL GAS - 9

GOSdruva MED A stabilizer is a pressure reduction unit with the task to equalize the eventual pressure variation in the hospital pipeline system to ensure a correct pressure from the terminal units. The stabilizer makes it possible to distribute gas with different pressure to department and buildings in the hospital area. In some cases it is needed to deliver a higher pressure from the main gas manifold to compensate for small pipe dimensions. In those cases the Stabilizer shall be mounted as close as possible before the first terminal unit, to ensure a correct pressure to...

Open the catalog to page 9
MEDICAL CENTRAL GAS - 10

MED GAS MANIFOLD MM40 - STABILIZER Manifold MM40 - STABILIZER is a second stage pressure reduction unit with the task to equalize the eventual pressure variation in the hospital pipeline system to ensure a correct pressure from the terminal units. MM40 - STABILIZER is only second stage reduction unit where the primary gas supply is provided by high pressure gas manifolds (such as MM40 - HP Unit). In case of signal for pressure deviation in relation to the alarm settings, the alarm can easily be displayed on a Gas alarm unit. It is also possible to send information to the central operation...

Open the catalog to page 10
MEDICAL CENTRAL GAS - 11

MED GAS MANIFOLD MM90 - HP UNIT FULLY AUTOMATIC The MM90 HP unit medical manifold is intended for use in hospital pipeline system as medical gas source. Together with MM90, always use an alarm providing all alarms according to standard (like gas alarm C44). As 2nd stage is recommended to use a stabilizer. The manifold will deliver gas from the operating bank to the manifold pressure regulator until the cylinders are exhausted. At that point the supply will switch to the reserve bank and the empty bank can be replenished. The object gives uninterrupted gas supply. Gas Alarm C44 is a standard...

Open the catalog to page 11
MEDICAL CENTRAL GAS - 12

GG©druva MED The MM90 HP unit medical manifold is intended for use in hospital pipeline system as medical gas source. Together with MM90, always use an alarm providing all alarms according to standard (like gas alarm C44). As 2nd stage is recommended to use a stabilizer. The manifold will deliver gas from the operating bank to the manifold pressure regulator until the cylinders are exhausted. At that point the supply will switch to the reserve bank and the exhausted bank can be replenished. The object gives uninterrupted gas supply. Gas Alarm C44 is a standard accessory. The gas alarm C44...

Open the catalog to page 12
MEDICAL CENTRAL GAS - 13

MED GAS MANIFOLD MM90 - STANDBY (BACKUP) The manifold MM90 STANDBY covered by this description is designed to be used as a third source of supply in medical central gas systems. The manifold will deliver gas when the nominal supply system pressure falls below a set level (7 bar). This is a back up source. Together with MM90 STANDBY always use the MM90 HP unit and alarm providing all alarms according to standard (like Gas alarm C44). As 2nd stage is recommended to use a stabilizer. Gas Alarm C44 is a standard accessory. The Gas alarm C44 gives visual and audible indication. It surveils and...

Open the catalog to page 13

All GCE Group catalogs and technical brochures

  1. APTECh

    8 Pages

  2. MEDIVITOP®

    4 Pages

  3. MEDIVITAL®

    4 Pages

  4. VALVES

    12 Pages

  5. Zeno_lite

    2 Pages

  6. MFC CATALOGUE

    16 Pages

  7. MEDIEVAC+

    2 Pages

  8. Medivital

    4 Pages

  9. VARIMED

    2 Pages

  10. NUVO 8

    2 Pages

  11. APS II

    4 Pages

  12. GSS

    2 Pages

  13. GAS ALARM G4

    2 Pages

  14. MEDIWET

    2 Pages

  15. Medimeter

    2 Pages

  16. MediEject

    2 Pages

  17. Elite

    2 Pages

  18. EASE II

    2 Pages

Archived catalogs