Product Description: The Console is a UL-listed horizontal assembly designed for medical gas and electrical services, accommodating standard components like medical gas outlets and electrical receptacles.
Construction: The backboxes are made from 16-gauge galvanized steel, with compartmentalized electrical components for different voltages. Panels for devices are also 16-gauge steel with a powder-coated finish, featuring anodized aluminum trim for easy servicing.
Medical Gas Connections: Includes pigtails for connection by others, with copper tubing protected against galvanic corrosion. Outlets are standard brand as specified in project drawings.
Electrical Connections: Devices are not pre-wired; all wiring and conduits are installed by others. Connections must be made before drywall installation, with provisions for low-voltage devices like nurse call systems.
Installation: Involves receiving, storage, and setup, with all materials supplied by the contractor. The electrical contractor handles wiring and testing per NFPA standards, while the medical gas contractor manages piping and certification according to NFPA 99.
See more

Catalog excerpts

Console-1

SPECIFICATIONS CONSOLE PRODUCT DESCRIPTION The Console is a UL-listed, horizontal medical gas and electrical service assembly to conveniently locate services such as medical gas, electrical and communications. The unit is designed to accept standard-depth components such as medical gas outlets, clocks, nurse call stations, electrical receptacles, light switches, etc. CONSTRUCTION Console backboxes are constructed of 16-gauge galvanized steel. Electrical components of different voltages are compartmentalized by means of metal barrier plates, which may be added or relocated to facilitate future electrical system modifications. Mounting panels for electrical devices and medical gas outlets are constructed of 16-gauge steel with a powder coated finish to match Formica #923 "Surf" laminate. Each panel includes a clear anodized extruded aluminum trim around the edges and contains a series of openings for attachment of electrical devices and device cover plates. Each panel mounts directly to the backbox, and device cover plates are attached directly to the face for ease of removal and servicing of devices. MEDICAL GAS CONNECTIONS Piping Medical gas outlets include pigtails only for connection by others. This piping is to be connected above the finished ceiling (by others) prior to drywall installation. Tubing ends are securely capped and properly identified. To prevent galvanic corrosion, all copper tubing is protected from contact with dissimilar metals. Medical Gas Outlets Outlets are manufacturer’s standard brand. Type and style are as called for on the project drawings.

 Open the catalog to page 1
Console-2

ELECTRICAL CONNECTIONS Wiring Line Voltage Electrical devices are not pre-wired. All conduits and wiring are furnished and installed by others at jobsite. Connection of conduit runs and wiring to the electrical service console is to be made before drywall installation is performed. All electrical connections are to be made between the unit and a field-installed junction box prior to drywall installation. Once these steps are performed, drywall installation may proceed. Low-Voltage Provisions Provisions for low-voltage communication devices consist of backboxes or barriered compartments. Communications...