Standard Lead Lined Steel Door Specification
Section 083449: Radiation Protection Metal Doors
Part 1 – General
1.00 Summary: The doors are constructed from commercial quality, hot dipped galvanized steel (HDGS) conforming to ASTM# A527, with door face sheet thickness options of 18, 16, or 14 gauge. They are available as non-rated or with UL fire ratings up to 3 hours. The lead thickness is specified by a qualified health radiation physicist and must comply with NCRP Reports No. 49 and 147, as well as local regulations. Visionlites must be lead-lined with X-Ray Safety Glass.
1.01 Product Handling: Special storage and handling requirements are necessary to prevent warpage, including keeping the doors flat and away from moisture.
Part 2 – Products
2.01 Acceptable Manufacturers: Ray-Bar Engineering Corporation, with over 70 years of experience in X-Ray Shielding Materials.
2.02 Materials: The doors feature 18 gauge HDGS faces, 16 gauge HDGS edges, and a core of 99.9% pure lead sheet. The finish includes a galvanized pre-treatment and rust-inhibitive primer.
2.03 Fabrication: Doors have reinforced vertical edges with 16 gauge steel channels and a honeycomb core with a lead sheet bonded to the skins. They are mortised for hardware application and comply with AWS welding standards.
Part 3 – Quality Assurance
3.00 Compliance: Doors meet NCRP Reports No. 49 and 147 standards and local regulations. Ray-Bar Engineering Corporation has over 20 years of experience in fabricating radiation protection materials.
Part 4 – Execution
4.01 Installation: Installation is the responsibility of the contractor.
4.02 Certification: Upon completion, a certificate of compliance will be provided, confirming adherence to specifications and the radiation shielding report.
See more

Catalog excerpts

Ray-Bar Lead Lined Hollow Metal Door Specifications-1

Ray-Bar Engineering Corporation 697 W Foothill Blvd PO Box 415 Azusa California 91702-0415 Toll Free Tel #(800)444-XRAY Ph#(626) 969-1818 E-mail: [email protected] Website: www.raybar.com Fax (800)333-XRAY(9729) STANDARD LEAD LINED STEEL DOOR SPECIFICATION SECTION 083449 RADIATION PROTECTION METAL DOORS PART 1 – GENERAL 1.00 SUMMARY A. Doors shall be made of commercial quality, level, hot dipped galvanized steel (HDGS) conforming to ASTM# A527 and door face sheet thickness of 18, 16 or 14 gauge, with no visible seams on either face and sheet lead meeting Federal Specification QQ-L-201f . Doors are available as non-rated, or with UL fire ratings of A, B or C labels up to 3 hour, only as specified in project door schedule. B. All doors will be 1-3/4” thickness, strong, rigid, neat in appearance, and free from warpage. Edge bends will be true and straight and of minimum radius for the gauge of metal used. C. Lead thickness as specified by a qualified health radiation physicist familiar with local standards and regulations. Lead thickness value will be clearly labeled on door 1. Must Comply with requirements of National Council on Radiation Protection and Measurement (NCRP) Report No.49“Structural Shielding Design and Evaluation for Medical Use of X-Rays and Gamma Rays of Energies up to 10 MeV”, and NCRP Report No. 147 “Structural Shielding Design for Medical X-Ray Imaging Facilities”. 2. Must Comply with requirements of local regulatory agencies where standards and criteria exceed NCRP Reports 49 and 147. 3. Lead thickness value is to be of same or greater value as in wall or partition door opening occurs in. 4.Visionlites must be lead-lined and require X-Ray Safety Glass labeled as impact resistant meeting the requirements of ANSI Z97.1 and CPSC 16 CFR 1201 Category 2. ( If fire-rated, additional clear ceramic fire-rated glazing is required). 1.01 PRODUCT HANDLING A. Follow special storage and handling requirements to prevent warpage. Keep flat until ready to use. Never store in sun or areas where moisture is present. PART 2 – PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS Ray-Bar Engineering Corporation, a manufacturer regularly engaged in the successful production of X-Ray Shielding Materials for over 70 years. Contact Toll Free 1(800)444-XRAY Phone (626) 969-1818 or Fax 1(800)333XRAY(9729) website: www.raybar.com, E-mail: [email protected] 2.02 MATERIALS A. Faces: 18 gauge (unless otherwise specified) thick Hot Dipped Galvanized Steel (HDGS). Prime quality, conforming to ASTM A527. Wilsonart Plastic Laminate may be factory added to faces only, if specified. B. Edges: 16 gauge thick Hot Dipped Galvanized Steel (HDGS) channel. Prime quality conforming to ASTM A527. C. Core: 99.9% Pure lead sheet per Federal Specification QQ-L-201f, Grade C. Reference radiation shielding report for thickness of lead. D. Finish: Galvanized pre-treatment and manufacturer’s standard rust inhibitive primer. 1

 Open the catalog to page 1
Ray-Bar Lead Lined Hollow Metal Door Specifications-2

A. The vertical edges will be reinforced by 16 gauge minimum continuous steel channel extending full height of the door. The top and bottom edges will be reinforced with 16 gauge channels spot welded to the face sheets. B. Internal construction for the door consists of 1/2“ cell honeycomb core with single layer unpierced sheet lead bonded to the door skins (lead sheet thickness as indicated on the Lead Protection Schedule). Apply lead sheet continuously from top to bottom and edge to edge, door lead thickness value will be clearly labeled C. All doors shall be mortised and reinforced to allow...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.