SMBA

SMBA

SMBA

Product catalog summary
Overview: The document discusses Surface Mounted Blast Attenuators (SMBA), which are stationary louvered attenuators designed to protect HVAC air intake and outlet openings in buildings subjected to blast design overpressure below 0.07 barg (7 kPag). These attenuators are used when blast protection valves do not close due to insufficient overpressure.
Design and Installation: SMBA can be installed flush with the wall or projecting from it, with the latter allowing for self-draining of sand trapped by the blades. They are designed to provide a tortuous flow path to create significant resistance to incoming blast waves, reducing downstream overpressure. They are suitable for both vertical and horizontal installations.
Construction: The attenuators consist of two or more opposite rows of V-shaped blades welded in a rectangular frame, made from heavy-gauge galvanized steel and factory-painted unless specified otherwise.
Performance: Typically, the airflow speed through the attenuators ranges from 2 to 4 m/s, resulting in a pressure drop from 70 to 200 Pa. The expected residual downstream pressure is approximately 50% of the incoming pressure wave. Special sizes are available upon request.
Additional Information: The document includes typical installation dimensions and notes that Sagicofi m S.p.A. reserves the right to change or modify product features and specifications without prior notice.
Contact Information: Sagicofi m S.p.A., Comfort Filtration Engineering, via Firenze 1, 20063 Cernusco sul Naviglio, Milan, Italy. Tel: +39 02 929021, Fax: +39 02 92902300, Email: info@sagicofi m.com, Website: www.sagicofi m.com
See more

Catalog excerpts

SMBA-1

SMBA Surface Mounted Blast Attenuators

 Open the catalog to page 1
SMBA-2

Surface Mounted Blast Attenuators The blast attenuators SMBA are stationary louvered type attenuators to be installed for the protection of HVAC air intake and outlet openings of the specified buildings subjected to a blast design overpressure lower than 0.07 barg (7 kPag), where the blast protection valves would not however close due to insufficient overpressure. Blast attenuators can be designed to be installed flush with the wall or projecting from it; in this second installation typology, blast attenuators are self-draining of the sand trapped by the blades. The blast attenuators construction...

 Open the catalog to page 2

All SagiCofim catalogs and technical brochures

  1. LS-KS

    1  Page

  2. DUG-B_DUG-A

    2  Pages

  3. SA SA - LF

    2  Pages

  4. LMG - KMG

    1  Page

  5. AH-AS

    1  Page

  6. INER-ST

    8  Pages

  7. MPS

    2  Pages

  8. PK

    3  Pages

  9. JD

    3  Pages

  10. FLG

    2  Pages

  11. CANISTER

    4  Pages

  12. SFD-SFDT

    16  Pages

  13. CARBO

    1  Page

  14. PFA6/6/7/8/9

    1  Page

  15. PFA/4-PFA/5

    1  Page

  16. CAP

    1  Page

  17. MULTIMOD

    1  Page

  18. MODULO

    1  Page

  19. CT

    1  Page

  20. SAF

    1  Page

  21. CAB

    1  Page

  22. DIF OT_LS

    8  Pages

  23. DIF O.T.

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.