RBC-AC1
2Pages

{{requestButtons}}

Catalog excerpts

RBC-AC1 - 1

This panel is designed to control two indoor units on a duty standby basis, one unit running while the remaining unit is on standby. Unit one will run for 100 hours, then change over to the standby unit which in turn will run for 100 hours. This pattern will be repeated on a continuous basis. If a duty unit sends a fault signal to the panel, the fault indicator lamp will illuminate and the panel will switch on the standby unit, the volt free contacts will make, the audible alarm will then sound. The control panel is also designed to monitor the room temperature. If the room temperature rises above the set adjustable point, all units will run , the volt free contacts will make, the audible alarm will sound. When the temperature drops back below the panel set point, operation will continue as normal. The audible alarm can be turned off using the mute switch on the panel facia. The panel is designed to be connected into a buildings fire alarm circuit. This will shut the units down in the event of an activation. Features: ■ Duty share every 100 hours. ■ Changeover on unit fault. ■ Volt free common fault output. ■ Duty and Fault indicators for each unit. ■ Digital thermostat to show room temperature Indication of panel Live, Alarm, Fire Alarm operated and individual Fire alarm contacts for shut down in fire situation. ■ Audible alarm for unit fault and high temperature with mute switch. ■ Door Interlocking isolator. Connections: ■ 2 No. Indoor units ■ Fire alarm circuit. ■ Room Sensor ■ Volt free fault contacts. Loose Supply Items: ■ Room Sensor. ■ 2 No. CN-61 leads ■ 2 No. SMTI leads Specification: ■ Electrical Supply: ■ Dimensions: (W X H X D) ■ Finish: ■ Cable entry: ■ W

Open the catalog to page 1
RBC-AC1 - 2

LEGEND Moor comsclig odds 4 Core screened cable 0.75mni nwxhngli 15M 4C Screened Cable to unit 1 4C Screened Cable to unit 2 • UnltfeuR •Unit Fault GSM Ariel (Cable and Ariel Suppled) Tamp Sensor (Sensor and Cable Supplied) 240V Supply from Switched fused Spir fta Alann Contact Normally Closed(240V) Note J01 must be cut at the Indoor unit

Open the catalog to page 2

All Toshiba Air Conditioning catalogs and technical brochures

  1. MMU-UP_MH

    2 Pages

  2. MMF-AP_H1

    1 Pages

  3. MMD-AP_SPH1

    1 Pages

  4. MML-AP_NH1

    1 Pages

  5. RAS- PKVPG-E

    2 Pages

  6. RBC-AC2

    2 Pages

  7. SHRMe

    9 Pages

  8. VRF

    1 Pages

  9. SHRMi

    2 Pages

  10. SMMS

    1 Pages

  11. MiNi-SMMS

    1 Pages