Xroom - 2

Unique solution electric or water exchanger recovery exchanger of heat and moisture easy installation design f its in to each interior available in two sizes ...is unique product containing ventilation unit and heating unit in one . Both systems work independently. Xroom is manufactured in two sizes Xroom 100 and Xroom 250. These units have wide range of usage in commercial and resi- Water exchanger is controlled by thermostatic water valve. Electric exchanger is controlled by controls of the unit. ROOM EPP filter covers Two types of recovery exchangers. Heat recovery or heat and moisture...

Open the catalog to page 2
Xroom - 3

...description of the unit and its feature... plastic duct exhaust air grill back draft shutter ODA - outdoor air (fresh, cold) SUP - supply air to inside (recuperated) ETA - exhaust air to outside (recupareted) The Xroom is ventilation unit with heat recovery. Its second feature is heating. The operation of Xroom is managed by CO2 sensor (Xroom ventilates only when the concentration of CO2 in the air inside the room is above hygienic recommended level), or enable manual control according the current feeling. Heating feature is controlled by thermostat, which manage water or electric...

Open the catalog to page 3
Xroom - 4

Frequently asked questions / Answers Decentral vs. central ventilation... Decentral ventilation is mechanical ventilation for one room only. Central ventilation is mechanical ventilation of more rooms by once device. Central ventilation is provided by units with bigger dimensions than units for decentral ventilation, since these has to supply higher air volume. Units for central ventilations are usually located in the technical room where they are not annoying the users by high noise level and they are not blocking any space. Central ventilation systems require ducting for supply and...

Open the catalog to page 4
Xroom - 5

Xroom is designed to be ventilation unit and the heating unit as well. The ventilation operation and the heating operation works independently one on each other. This means, that during ventilation request the heating does not have to work and oppositely. Both systems can operate at same time as well. The water and electric heater do not operate as the post heaters only, they operate as solid-regular air heaters. It is good to know, that Xroom unit 2in1 can replace the radiator (or electric convector) and save the space thus. Installation of the unit is simplified, that handyman can install...

Open the catalog to page 5
Xroom - 6

Control description Xroom ELECTRIC VERSION AUTOMAT/MANUAL By pressing the button, you come to the manual mode – ventilation is manually controlled by user, out-puts from the AQS sensors are ignored. By pushing the button once again you can active automatic mode – ventilation on demand based on AQS sensors. Indicator of air flow setting Indicator of heating setting ON/OFF / switching setting modes Setting of airflow and temperature FILTERS CLOGGING Indication of clogged filter is activated by timer, roughly after 6 month operations (only if the units ventilate). Indication is signaled by red...

Open the catalog to page 6
Xroom - 7

Technical data Xroom XROOM-100 a XROOM-250 XROOM-100 Type of recovery exchanger VENTILATION AND HEATING UNIT WITH HEAT AND HUMIDITY RECOVERY Unit equipment Xroom-100-heat and moisture recovery efficiency Type Type of recovery exchanger HRV (heat recovery) Flow (m3/h) AirFlow - setting cold climate A+ (-47 HRV, -45,9 ERV) ; medium climate A (-40,4 HRV, -38,9 ERV) ; warm climate A (-34,1 HRV), warm climate B(-33,1 ERV) Noise level*** Heating output range** Nominal heating output / boost* Unit equipment Type of recovery exchanger Energy efficiency class (SEC) Nominal current / boost* Nominal...

Open the catalog to page 7
Xroom - 8

Data - ACOUSTICS Data - WATER EXCHANGER Maximum usable water temperature 80 ° C XROOM-100 XR1-010-EC... - radiating the unit into the interior (inside the room) Airflow - setting Maximum operating pressure for the heater 1.6 MPa The connection dimension of both heat exchangers is an external thread G 3/4“ Sound power level LWA (dB A) Sound pressure level in a free field on a reflecting plane XR1-010-EC... - radiating the unit to the exterior (intake, exhaust outside) Airflow - setting 4. 7. (nominal airflow) Boost * Water pressure drop Heating output Water flow Water pressure drop...

Open the catalog to page 8
Xroom - 9

Data - WATER EXCHANGER XROOM-100-ERV Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Data - WATER EXCHANGER 75/65 Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow...

Open the catalog to page 9
Xroom - 10

Packaging and dimensions Weight Type Instalation Pieces on a pallet (max. stackability) Package size (width x length x height) Xroom has to be operated in indoor and dry space with temperature between +5°C up to +40°C. The unit can be installed only in horizontal position. When breaking the security distances the unit can operate unproperly and the fans might come damaged, the noise level might Necessary accessories Xroom unit Xroom unit Xroom unit increase or the service-access might get blocked off. Xroom equipped with heat exchanger (HRV) can produce the condensate and it is necessary to...

Open the catalog to page 10
Xroom - 11

front cover color RAL 9003 front cover color RAL 7016 design type S standard control W wifi control (in preparation) A antivandal (in preparation) CO CR X P HR ER S0 V1 E1 EC 010 025 XR1 without preheater with preheater heat recovery heat and moisture recovery without heater water heater electric heater unit Xroom - mark 1 ...for better concentration... Available in two colors ...fresh air without opening windows...

Open the catalog to page 11
Xroom - 12

Xvent s.r.o. Poděbradská 289 53009 Pardubice Czech Republic

Open the catalog to page 12

All Xvent catalogs and technical brochures

  1. Xhouse

    10 Pages

  2. Xflat

    9 Pages