Overview: The Xroom unit is a combined heating and ventilation system designed for single-room applications, featuring heat and moisture recovery for energy efficiency. It is suitable for both residential and commercial use, available in two sizes: Xroom 100 and Xroom 250. The unit is noted for its quiet operation and energy class A+ rating.
Specifications: Constructed from expanded polypropylene (EPP) with a removable aluminum front cover, the unit includes two energy-efficient EC fans and offers two types of recovery exchangers: standard heat recovery and enthalpic recovery for moisture regeneration. It is equipped with CO2 sensors and can accommodate additional RH and Radon sensors.
Installation: Installation is simplified with a metal template for correct positioning of intake and exhaust holes. The unit connects to the outdoor environment through plastic ducts with flaps to prevent cold drafts. Installation can be completed in under two hours without specialist assistance.
Operation and Control: The Xroom operates independently for ventilation and heating, controlled by a CO2 sensor or manually. The heating feature uses either a water or electric exchanger, managed by a thermostat. The control panel allows for airflow management, temperature settings, and indicates filter status and operational states.
Maintenance: Designed to be maintenance-free except for filter replacement, which is signaled by a flashing diode. Filters are easily accessible and replaceable, with a reset button to confirm replacement.
Advantages of Decentralized Ventilation: Suitable for individual rooms, offering on-demand ventilation based on air quality sensors, leading to energy savings. Easier to install and maintain compared to central ventilation systems.
Heat and Moisture Recovery: The unit's heat recovery system can save up to 85% of heating costs compared to traditional window ventilation. Enthalpic regeneration helps maintain indoor humidity levels, preventing issues associated with dry air.
Cost and Efficiency: Offers significant energy savings, with low operational costs due to efficient fans and reduced heating requirements. The initial investment is offset by long-term savings in energy costs.
Operational Modes: Features multiple airflow settings, including a BOOST mode for intensive ventilation, activated by holding a button for 3 seconds, running for 10 minutes unless manually deactivated.
Efficiency and Power Consumption: Lists heat recovery efficiency (HR efficiency) and enthalpy recovery efficiency (ER efficiency) for various airflow settings. Power input and current requirements are specified for each setting, highlighting the energy efficiency of the units.
Acoustic Data: Provides sound power levels and sound pressure levels for different operational settings, crucial for understanding the noise impact of the units in different environments.
Water Exchanger Data: Includes detailed information on the water exchanger's performance, covering heating output, exhaust air temperature, water flow, and pressure drop across various temperature and airflow conditions.
Energy Efficiency Class: Classified according to their energy efficiency in different climates, with ratings provided for cold, medium, and warm climates.
Key Features: Includes features such as automatic/manual switching, airflow and temperature settings, and indicators for fan status and filter clogging. Specifies the maximum usable water temperature and operating pressure for the heater.
Technical Document Summary:
1. Specifications: Detailed specifications for the Xroom units, including airflow rates, heating outputs, exhaust air temperatures, water flow, and pressure drops at various air intake temperatures (10°C, 15°C, 20°C). Available in two models: XR-010 and XR-025, with different dimensions and weights.
2. Packaging and Dimensions: Different sizes and weights, with specific packaging dimensions. The XR-010 model has a diameter of 125 mm, while the XR-025 model has a diameter of 150 mm. Packaging includes the unit, mounting material, a quick manual, and safety instructions.
3. Installation Guidelines: Must be installed indoors in a dry space with temperatures between +5°C and +40°C. Should be installed horizontally to avoid operational issues. Units equipped with a heat exchanger may produce condensate, which can leak through the outlet grill.
4. Accessories: Necessary accessories include ducts and air grilles. Filters are available in M5 and F7 types, and there are specific accessories for radon and air quality systems.
5. Unit Coding and Options: Explains the coding system for Xroom units, detailing options for control types, heater types, and airflow capacities. Available with or without preheaters and in two color options.
6. Applications: Suitable for various environments such as offices, living rooms, hotels, hospitals, and schools, providing benefits like improved air quality and productivity.
Contact Information: Xvent s.r.o., Poděbradská 289, 53009 Pardubice, Czech Republic. Phone: +420 467 070 233, Email: [email protected]
See more

Catalog excerpts

Xroom-1

Single room heating and ventilation unit with heat and moisture recovery www.xvent.cz

 Open the catalog to page 1
Xroom-2

Unique solution electric or water exchanger recovery exchanger of heat and moisture easy installation design f its in to each interior available in two sizes ...is unique product containing ventilation unit and heating unit in one . Both systems work independently. Xroom is manufactured in two sizes Xroom 100 and Xroom 250. These units have wide range of usage in commercial and resi- Water exchanger is controlled by thermostatic water valve. Electric exchanger is controlled by controls of the unit. ROOM EPP filter covers Two types of recovery exchangers. Heat recovery or heat and moisture recovery....

 Open the catalog to page 2
Xroom-3

...description of the unit and its feature... plastic duct exhaust air grill back draft shutter ODA - outdoor air (fresh, cold) SUP - supply air to inside (recuperated) ETA - exhaust air to outside (recupareted) The Xroom is ventilation unit with heat recovery. Its second feature is heating. The operation of Xroom is managed by CO2 sensor (Xroom ventilates only when the concentration of CO2 in the air inside the room is above hygienic recommended level), or enable manual control according the current feeling. Heating feature is controlled by thermostat, which manage water or electric exchanger....

 Open the catalog to page 3
Xroom-4

Frequently asked questions / Answers Decentral vs. central ventilation... Decentral ventilation is mechanical ventilation for one room only. Central ventilation is mechanical ventilation of more rooms by once device. Central ventilation is provided by units with bigger dimensions than units for decentral ventilation, since these has to supply higher air volume. Units for central ventilations are usually located in the technical room where they are not annoying the users by high noise level and they are not blocking any space. Central ventilation systems require ducting for supply and extract...

 Open the catalog to page 4
Xroom-5

Xroom is designed to be ventilation unit and the heating unit as well. The ventilation operation and the heating operation works independently one on each other. This means, that during ventilation request the heating does not have to work and oppositely. Both systems can operate at same time as well. The water and electric heater do not operate as the post heaters only, they operate as solid-regular air heaters. It is good to know, that Xroom unit 2in1 can replace the radiator (or electric convector) and save the space thus. Installation of the unit is simplified, that handyman can install it...

 Open the catalog to page 5
Xroom-6

Control description Xroom ELECTRIC VERSION AUTOMAT/MANUAL By pressing the button, you come to the manual mode – ventilation is manually controlled by user, out-puts from the AQS sensors are ignored. By pushing the button once again you can active automatic mode – ventilation on demand based on AQS sensors. Indicator of air flow setting Indicator of heating setting ON/OFF / switching setting modes Setting of airflow and temperature FILTERS CLOGGING Indication of clogged filter is activated by timer, roughly after 6 month operations (only if the units ventilate). Indication is signaled by red diode...

 Open the catalog to page 6
Xroom-7

Technical data Xroom XROOM-100 a XROOM-250 XROOM-100 Type of recovery exchanger VENTILATION AND HEATING UNIT WITH HEAT AND HUMIDITY RECOVERY Unit equipment Xroom-100-heat and moisture recovery efficiency Type Type of recovery exchanger HRV (heat recovery) Flow (m3/h) AirFlow - setting cold climate A+ (-47 HRV, -45,9 ERV) ; medium climate A (-40,4 HRV, -38,9 ERV) ; warm climate A (-34,1 HRV), warm climate B(-33,1 ERV) Noise level*** Heating output range** Nominal heating output / boost* Unit equipment Type of recovery exchanger Energy efficiency class (SEC) Nominal current / boost* Nominal power...

 Open the catalog to page 7
Xroom-8

Data - ACOUSTICS Data - WATER EXCHANGER Maximum usable water temperature 80 ° C XROOM-100 XR1-010-EC... - radiating the unit into the interior (inside the room) Airflow - setting Maximum operating pressure for the heater 1.6 MPa The connection dimension of both heat exchangers is an external thread G 3/4“ Sound power level LWA (dB A) Sound pressure level in a free field on a reflecting plane XR1-010-EC... - radiating the unit to the exterior (intake, exhaust outside) Airflow - setting 4. 7. (nominal airflow) Boost * Water pressure drop Heating output Water flow Water pressure drop XR1-025-EC......

 Open the catalog to page 8
Xroom-9

Data - WATER EXCHANGER XROOM-100-ERV Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Data - WATER EXCHANGER 75/65 Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water pressure drop Heating output Water flow Water...

 Open the catalog to page 9
Xroom-10

Packaging and dimensions Weight Type Instalation Pieces on a pallet (max. stackability) Package size (width x length x height) Xroom has to be operated in indoor and dry space with temperature between +5°C up to +40°C. The unit can be installed only in horizontal position. When breaking the security distances the unit can operate unproperly and the fans might come damaged, the noise level might Necessary accessories Xroom unit Xroom unit Xroom unit increase or the service-access might get blocked off. Xroom equipped with heat exchanger (HRV) can produce the condensate and it is necessary to realized,...

 Open the catalog to page 10
Xroom-11

front cover color RAL 9003 front cover color RAL 7016 design type S standard control W wifi control (in preparation) A antivandal (in preparation) CO CR X P HR ER S0 V1 E1 EC 010 025 XR1 without preheater with preheater heat recovery heat and moisture recovery without heater water heater electric heater unit Xroom - mark 1 ...for better concentration... Available in two colors ...fresh air without opening windows...

 Open the catalog to page 11
Xroom-12

Xvent s.r.o. Poděbradská 289 53009 Pardubice Czech Republic

 Open the catalog to page 12

All Xvent catalogs and technical brochures

  1. Xhouse

    10  Pages

  2. Xflat

    9  Pages

  3. MiracleAir-EN

    3  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.